Fire-rated doors explained: ratings, standards and specs
A fire-rated door is a complete doorset (leaf, frame, seals, hinges, closer and any glass) that has passed a standard fire test for a stated time. In the European system, EI60 means 60 minutes of integrity and insulation under EN 1634-1, which Egypt adopted as ES 6315-1/2024. Which rating each opening needs is set by the applicable code and the project's fire strategy.
Key points
- European ratings are minutes achieved in a test: EN 13501-2 periods run from 15 to 240 minutes; US UL 10C ratings run from 20 minutes to 4 hours.
- Write the full class, such as EI2 60-Sa-C5: insulation method (I1 or I2), smoke class and self-closing are separate parts.
- Egypt adopted EN 1634-1 as ES 6315-1/2024; England removes BS 476 fire-resistance classes from 2 September 2029.
- The rating belongs to the tested doorset. Changing hardware or glass without evidence can void it.
- In Egypt, confirm required ratings and documents with your fire consultant and Civil Protection for each project.
- GCC export needs third-party testing, certification and usually a factory audit before Civil Defence listing.
What is a fire-rated door made of?
A fire-rated door is a doorset: the leaf, frame and every component fitted to it, tested together. The tested assembly is the door together with all its components, such as hardware, fixings, seals and architraves or trim.
In a timber doorset, the leaf typically has a fire-resisting core, edge lippings and a facing veneer or laminate. Intumescent seals in the frame or leaf edge expand with heat to close the gap around the leaf; separate smoke seals limit cold smoke. The core, thickness and seals must match what was tested, which is what the test report or certificate proves.
Fire door ratings explained: E, EI1, EI2, EW and smoke
A rating is the number of minutes a doorset met set criteria in a standard fire test. In the European system, EN 13501-2 sets the classes and EN 1634-1 is the test.
- E: integrity. Stops flames and hot gases passing. Classes: 15, 20, 30, 45, 60, 90, 120, 180 and 240 minutes.
- EI: integrity and insulation. Also limits the temperature rise on the unexposed side, for the same periods. The I is written I1 or I2 to show which insulation definition was used, so a precise specification reads "EI1 30" or "EI2 60".
- EW: integrity and limited radiation. 20, 30 and 60 minutes.
- Sa or S200: smoke control. Tested separately to EN 1634-3.
- C: self-closing. Optionally graded C0 to C5 by use category.
What do EI30 and EI60 mean? The doorset kept integrity and insulation for 30 or 60 minutes in the test. A full class such as "EI2 60-Sa-C5" adds the insulation method, smoke control and self-closing.
What is FD30? The older British naming. In UK practice a 30-minute requirement is written as FD30 or E30, tested to BS 476 Part 22 or to the European equivalent BS EN 1634 Part 1. So FD30 expresses integrity, not insulation.
Which standard applies: EN 1634-1, ES 6315-1, BS 476-22, UL 10C or NFPA 252?
Use the standard named in your project specification. Egypt has adopted EN 1634-1 as ES 6315-1/2024, based on EN 1634-1:2014+A1:2018 and endorsed on 26 February 2024, so EN testing with EN 13501-2 classification is the most direct route for Egyptian projects. Projects designed to US practice, which the Egyptian code accepts as a reference for performance-based design, may specify UL 10C or NFPA 252 ratings with installation to NFPA 80.
| Standard | System | What it does | How ratings are written | Status |
|---|---|---|---|---|
| EN 1634-1 | European | Fire-resistance test for door and shutter assemblies | Classified under EN 13501-2: E / EI1 / EI2 / EW + minutes | Current |
| ES 6315-1/2024 | Egypt (EOS) | Egyptian adoption of EN 1634-1 | As EN 13501-2 | Endorsed 26 Feb 2024 |
| EN 13501-2 | European | Classification of fire-resistance results | E, EI, EW 15–240 min; smoke Sa / S200; C0–C5 | Current |
| BS 476-22 | British (legacy) | Fire-resistance test for non-loadbearing elements, incl. doors | FD + minutes, e.g. FD30 | Removed from England's Approved Document B from 2 Sep 2029 |
| UL 10C | US | Positive-pressure fire test of door assemblies | 4, 3, 1½, 1, ¾ h, 30 or 20 min; temperature-rise 250 / 450 / 650 °F at 30 min | Current |
| NFPA 252 | US | Fire endurance and hose-stream test of door assemblies; can run at positive pressure | Hours / minutes | Current |
| NFPA 80-2025 | US | Installation and maintenance of fire doors | Not a test | 2025 edition |
Is BS 476-22 still valid? It is still a recognised test, but England removes BS 476 fire-resistance classes from Approved Document B from 2 September 2029, with a transition for projects already underway (reaction-to-fire classes went on 2 March 2025). Under the BM TRADA Q-Mark certification scheme, doorsets must be classified to EN 13501-2 by that date. For new specifications, EN evidence is the safer long-term choice where the project allows it.
What does a complete fire doorset include?
Every item is part of the rating. Changing one without test or assessment evidence can invalidate it.
- Leaf and core: the construction, thickness and lipping tested.
- Frame: section, fixings and the wall type it was tested in.
- Intumescent and smoke seals: size and position as tested; smoke seals where Sa or S200 is specified.
- Hinges: conformity-marked, tested to BS EN 1935.
- Closers, hold-open devices, coordinators: conformity-marked to BS EN 1154, 1155 and 1158.
- Locks and exit hardware: only items covered by the evidence.
- Vision panels: fire-rated glass and glazing system of the tested type and size.
- Signage: NFPA 80 limits signs to less than 5% of the door face.
- Labels: a permanent mark on leaf and frame linking the door to its certificate.
What are the types of fire-rated doors?
Fire-rated doors are grouped by material, by how they open and by rating. Whatever the type, the rating comes from a tested and classified doorset, not from the type or the material.
| Type | What it is | What to check |
|---|---|---|
| Timber doorset | Timber leaf with a fire-resisting core, lippings and intumescent seals, supplied with its frame | Test evidence for that core, thickness and frame |
| Steel door | Steel leaf and frame; common types are hollow-metal, sheet-metal and metal-clad | Label on leaf and frame; field changes can void it |
| Glazed door | Timber or steel leaf with fire-rated glass in a tested glazing system | Glass type and size within the evidence; under UL certification, glass lights over 100 sq in. in doors rated over 45 minutes must themselves be fire-resistance rated |
| Double-leaf (pair) | Two leaves in one frame | A coordinator so the leaves close in order (BS EN 1158) and seals at the meeting edges |
| Sliding or rolling shutter | For large openings; sliding-type fire doors and rolling steel fire doors are certified as separate categories | Classification as a shutter or door assembly under EN 13501-2 or UL |
| Smoke-control door | A fire door also tested for smoke leakage to EN 1634-3 | Class Sa or S200 in the classification |
| Emergency exit door | A fire door on an escape route with panic or emergency exit hardware | EN 1125 or EN 179 hardware covered by the door's evidence (see below) |
By rating: European classes run from E15 to EI 240, US UL 10C ratings from 20 minutes to 4 hours, and older British specifications write FD20 or FD30 (see ratings above). Doorset or leaf only? A doorset is supplied as leaf, frame and hardware together; in Europe, EN 16034 is the product standard for fire-resisting pedestrian doorsets. A leaf bought alone is only rated if it is fitted into the frame and with the components its evidence covers.
Fire-rated wooden doors vs steel fire doors
Both can carry the same rating. The rating comes from the test evidence for that construction, not from the material.
| Point | Timber doorset | Steel doorset |
|---|---|---|
| Proof of rating | Test report or certificate for that leaf, frame and hardware | Same |
| Finish | Can match the veneer and profiles of the building's other doors | Painted or coated metal |
| Site changes | Trimming, holes or new hardware only within the evidence | Same; field modifications can void the label |
| Glazing | With tested vision-panel systems | With tested vision-panel systems |
Where are fire doors required, and which rating?
Which openings need a fire door, and at what rating, is set by the applicable code and the project's fire strategy, not by the supplier. The consultant's door schedule should give the rating, smoke class and self-closing requirement for each door.
For orientation only, UK practice recommends 20 minutes (FD20 or E20) in some situations and 30 minutes (FD30 or E30) in others. Egyptian and GCC requirements come from their own codes.
Fire-rated emergency exit doors: panic bars, EN 1125 and EN 179
An emergency exit door («باب طوارئ») on an escape route is usually also a fire door, so it needs a fire rating and exit hardware tested for escape. Two European standards cover that hardware.
- EN 1125: panic exit devices. Operated by a horizontal push-bar or touch-bar, "specifically designed for use in a panic situation on escape routes", for hinged or pivoted doors including double doorsets.
- EN 179: emergency exit devices. Operated by a lever handle or push pad, for "a safe exit under an emergency situation on escape routes".
- Which one? As a rule of thumb, EN 179 devices suit restricted areas where all users know the building, and panic devices suit public areas; if the users are uncertain, specify EN 1125. The fire strategy decides for each door.
- On a fire door: whether a panic device suits a fire or smoke door depends on fire tests in addition to the EN 1125 tests. The device must also be covered by the doorset's own evidence.
- Electric locking: electrically controlled exit systems fall under separate standards, not EN 1125.
Emergency exit doors are priced per project, because cost depends on the specification: the rating, single or double leaf, the exit device, closer and coordinator, glazing and signage.
Fire-rated doors in Egypt: which code, and who approves?
Egyptian projects follow the Egyptian fire code and the requirements of Civil Protection (Egypt), «الحماية المدنية». Detailed fire-door requirements and any product-approval procedure are confirmed project by project, so confirm them with your fire consultant and Civil Protection before ordering.
- The code: the "Egyptian Code for the foundations of design and implementation requirements to protect buildings from fire". It is prescriptive, accepting performance-based design only where it complies with a recognised international code such as NFPA, and linked to Unified Building Law 119/2008.
- Industrial buildings: HBRC prepared a new Egyptian code for industrial and storage facilities, discussed with the Federation of Egyptian Industries on 5 March 2025.
- Civil Protection: HBRC co-ran a 2021 fire safety forum with the General Administration of Civil Protection.
- Test standard: ES 6315-1/2024 (EN 1634-1).
Ask the consultant which standard and documents Civil Protection will expect, and have the supplier confirm them in writing in the quotation. If a supplier cites a local test, ask for the full report and check which standard it used.
Exporting fire doors to the GCC: UAE and Saudi Civil Defence
GCC Civil Defence authorities expect fire-rated products to be tested and certified by an approved lab and certification body, usually with an initial factory audit, before the manufacturer applies to the authority.
- UAE: a Civil Defence Certificate of Conformity is required per listed product, with testing for each manufacturing location; the certificate does not expire but is subject to Civil Defence's latest requirements (rules as of September 2018), so check the current list. The UAE Fire and Life Safety Code update (announced January 2017) included the fire door chapters.
- Saudi Arabia: Civil Defense recognises third-party schemes such as the Applus Fire Safety mark (March 2020). An updated Saudi Fire Code (SBC-801) was announced for mid-2025. SASO's fire-equipment regulation does not cover doors.
- Certification schemes for doors include BM TRADA Q-Mark, Warrington CERTIFIRE, IFC, BRE/LPCB, UL and Intertek Warnock Hersey.
What affects the price of a fire-rated door?
EI30 and EI60 doors are priced per project, because cost depends on the specification: the rating and smoke class, size and leaf count, finish, glazing, hardware, and the certification documents required. Shalaby Industries prices each door against your door schedule.
Fire door inspection and maintenance checklist
Inspect after installation, after maintenance and at the interval your code sets. NFPA 80 requires inspection and testing on completion of installation and of maintenance work; recurring annual inspection comes from the fire code that references it. In the UK, regular inspection is a legal duty under Article 17 of the Fire Safety Order.
- Labels on leaf and frame present and legible.
- No holes or damage; glazing and beads secure.
- No missing or broken parts; clearances within limits.
- Door self-closes fully and latches; coordinator closes pairs in order.
- No hardware interfering with closing; no unapproved field changes.
- Seals present, continuous and the right type.
- Signage under 5% of the door face; door never wedged open.
Buyer checklist: what to ask a fire door supplier
- The full classification, e.g. "EI2 60-Sa-C5 to EN 13501-2, tested to EN 1634-1 / ES 6315-1".
- The test report or third-party certificate, naming the lab or body.
- Proof the offered core, frame, seals and glazing match the evidence.
- The approved hardware schedule.
- Labelling, installation method and gap tolerances.
- Egypt: written confirmation of the documents Civil Protection will expect.
- GCC: the Civil Defence certificate or route for the target country.
Shalaby Industries makes wooden doors in its factory in the 6th of October industrial zone and quotes fire-rated timber doorsets to the rating and standard in your specification, confirming the test standard and submittal documents in the quotation before production. See fire-rated wooden doors in Egypt, Shalaby Industries and Shalaby Contracting, or read choosing a fit-out contractor and finishing costs in Egypt.
Fire-rated door FAQ
What is the difference between E30 and EI30?
Both mean the door stopped flames and hot gases passing for 30 minutes in the test. EI30 also limited the temperature rise on the side away from the fire. Under EN 13501-2, the insulation part is written I1 or I2 to show the measurement method, so a precise specification reads EI1 30 or EI2 30.
Which fire door standard applies in Egypt?
Follow the standard in the project specification. Egypt has adopted EN 1634-1 as ES 6315-1/2024, so EN testing with EN 13501-2 classification is the most direct route. Projects designed to US practice may specify UL 10C or NFPA 252 ratings with installation to NFPA 80. Confirm the expected standard with your consultant.
Do fire doors in Egypt need Civil Defence approval?
In Egypt the authority is Civil Protection, «الحماية المدنية», often searched as Civil Defence. It reviews fire safety for buildings under the Egyptian fire code. The approval route for door products is confirmed project by project, so ask your fire consultant which documents Civil Protection will expect and have the supplier confirm them in writing.
Is a fire rating still valid if I change the lock or hinges?
Only if the new hardware is covered by the doorset's test or assessment evidence. The rating belongs to the whole tested assembly. Hinges should be tested to BS EN 1935 and closers to BS EN 1154 where European evidence applies. Unapproved field changes, extra holes or non-listed hardware can void the label.
How often should fire doors be inspected?
NFPA 80 requires inspection and testing when installation is complete and after maintenance work. Recurring annual inspection comes from the adopted fire code that references NFPA 80. In the UK, regular inspection is a legal duty under Article 17 of the Fire Safety Order. In Egypt, follow your code, consultant and Civil Protection.
What do I need to export fire doors to the UAE or Saudi Arabia?
GCC Civil Defence authorities expect fire-rated products to be tested and certified by an approved lab and certification body, usually after a factory audit. The UAE requires a Civil Defence Certificate of Conformity per product and per manufacturing location (rules as of 2018). Saudi Civil Defense recognises third-party schemes. Confirm current rules before production.
Are WPC doors fire rated?
Not by default. WPC as a material does not make a door fire-rated. A WPC door counts as fire-rated only if that exact doorset, with its frame, seals and hardware, has a test report or third-party certificate to a fire-resistance standard such as EN 1634-1, BS 476-22 or UL 10C. "Fire-retardant" material claims are not a door rating; ask for the certificate.
How much does an emergency exit door cost?
Fire-rated emergency exit doors depend on the specification and are priced per project. Price depends on the fire rating, size, single or double leaf, the exit device (EN 1125 push bar or EN 179 lever or push pad), closer and coordinator, glazing and signage. Shalaby Industries prices each door against your schedule.
How much does a fire-rated door cost in Egypt?
EI30 and EI60 doors depend on the specification and are priced per project. Price depends on the rating and smoke class, size, single or double leaf, finish, glazing, hardware and the certification documents required. Shalaby Industries prices each door against your door schedule after reviewing the specification.
What do you need to quote fire-rated doors?
Send the drawings and a door schedule with quantities, sizes and the fire rating for each door, plus the required standard, finishes, hardware and the delivery location. We confirm the test standard and the submittal documents in writing in the quotation, before production starts in our 6th of October factory.